6 Adjustments

6.6.2 Anti-Resonance Control Adjustment Function Operating Procedure

6.6.2 Anti-Resonance Control Adjustment Function Operating Procedure

With this function, a control reference is sent, and the function is executed while vibration is occuring.
Anti-resonance control adjustment function is performed from the Digital Operator (option) or SigmaWin+.
The function cannot be performed from the Panel Operator.
The operating procedure from the Digital Operator is described here.
Refer to the
ations of the Digital Operator.
The following three methods can be used for the anti-resonance control adjustment function. Select and use
the best method.
1. With Undetermined Vibration Frequency Before Adjusting Anti-Resonance Control → See Page 6-46.
2. With Determined Vibration Frequency Before Adjusting Anti-Resonance Control → See page 6-48.
3. For Fine-tuning After Adjusting the Anti-Resonance Control → See page 6-50.
(1) With Undetermined Vibration Frequency Before Adjusting Anti-Resonance Control
Step
1
2
3
4
5
6-46
Σ
-V series User's Manual, Operation of Digital Operator (SIEP S800000 55) for basic key oper-
Display after Operation
Status Display
Keys
Press the
utility function mode.
Use the
or
select Fn204.
Press the
Key to display the initial setting screen
for tuning mode.
Note: If the display does not switch and NO-OP is
displayed, refer to 6.6.1 (1) Before Performing
Anti-Resonance Control Adjustment Function.
Press the
or
"0".
Press the
played. The screen shown on the left will appear. The
detection of vibration frequencies will start and
"freq" will blink. Return to step 3 if vibration is not
detected.
Note: Lower the vibration detection sensitivity
(Pn311). When this parameter is lowered, the
detection sensitivity will be increased. Vibra-
tion may not be detected accurately if too small
value is set.
The vibration frequency will be displayed if vibration
is detected.
Operation
Key to view the main menu for the
Key to move through the list,
Key and select the tuning mode
Key while "Tuning Mode = 0" is dis-
Error
Error
Error
Torque reference
Torque reference
Positioning completed
Positioning completed
Positioning completed
signal
signal
signal
Waveform