7.15 Resetting Configuration Error of Option Module (Fn014)

The SERVOPACK with option module recognizes installation status and types of option module which is con-
nected to SERVOPACK. If an error is detected, the SERVOPACK issues an alarm.
This function resets these alarms.
For alarm types and corrective actions, refer to 10 Troubleshooting.
Note 1. Alarms related to option module can be cleared only by this function. These alarms cannot be cleared by alarm
2. Before clearing the alarm, perform corrective action for the alarm.
(1) Operating Procedure
Follow the steps below.
Step
1
2
3
4
5
6
7
8
9
7-24
)
reset or turning OFF the main circuit power supply.
Display after
Operation
MODE/SET
MODE/SET
MODE/SET
MODE/SET
MODE/SET
Display blinks
MODE/SET
MODE/SET
Turn OFF the power and then turn ON again to validate the setting.
Keys
Press the MODE/SET Key to select the utility function
mode.
DATA/
Press the UP or DOWN Key to select Fn014.
Note: When "no-oP" blinks for approximately one second,
the write prohibited setting is set in Fn010. Change
the setting in Fn010, and press the key again after
DATA/
enabling writing. (Refer to 7.12.)
Press the DATA/SHIFT Key for approximately one second.
The display shown on the left appears.
DATA/
Press the UP or DOWN Key to select option module to be
cleared.
DATA/
Press the MODE/SET Key for approximately one second.
The display shown on the left appears.
DATA/
Press the MODE/SET Key again. The display changes as
shown on the left and the configuration error of option mod-
ule is cleared.
DATA/
The display changes from "done" to the display shown on
the left.
Press the DATA/SHIFT Key for approximately one second.
"Fn014" is displayed again.
DATA/
Operation