Warning
Warning Name
Display
A.971
Undervoltage
Situation at Warning
Occurrence
• For 100 VAC SER-
VOPACKs:
The AC power supply
voltage is 60 V or
below.
• For 200 VAC SER-
VOPACKs:
The AC power supply
Measure the power supply voltage.
voltage is 140 V or
below.
• For 400 VAC SER-
VOPACKs:
The AC power supply
voltage is 280 V or
below.
The power supply volt-
age dropped during
Measure the power supply voltage.
operation.
An instantaneous power
Measure the power supply voltage.
failure occurred.
The fuse in the SERVO-
PACK is burned out.
A SERVOPACK fault
occurred.
Cause
Use a power supply voltage within the
specified range.
Increase the power supply capacity.
Lower the instantaneous power cut
hold time (Pn509).
Replace the SERVOPACK and con-
nect an AC/DC reactor to the SERVO-
PACK.
The SERVOPACK may be faulty.
Replace the SERVOPACK.
10.2 Warning Displays
Corrective Actions
10-23