Checking The Residual Current Circuit Breaker - ABB ProKiln GAC400 Operating Instruction

Probe gas sampling system
Table of Contents

Advertisement

ProKiln GAC400 PROBE GAS SAMPLING SYSTEM | OI/GAC400-EN REV. A
Retrieving data from the USB data-storage dongle
1. Open the control cabinet and find the back side of the HMI.
2. Locate the data storage dongle
underneath the HMI.
1
3. Remove the dongle and bring to an office computer.
4. Download CSV files to a computer for evaluation.
5. Re-insert the dongle into the USB slot by reversing the
previous steps.
The following data is logged to the USB memory stick of the
ProKiln GAC400 system for 60 days:
Title
Comment
T10 Tank temp.
Tank temperature
T11 Forward temp. Water forward temperature
T12 Return temp.
Water Return temperature
F12 Water flow
Water Flow l/min
ProbePosition
Probe Position in mm
Diff. T12-T11
Delta water temp T12-T11
T01 Actual
T01 H1 actual temperature
T01 Setpoint
T01 H1 Set point
T01 Output
T01 H1 Output
T02 Actual
T02 H2 actual temperature
T02 Setpoint
T02 H2 Set point
T02 Output
T02 H2 Output
T03 Actual
T03 H3 actual temperature
T03 Setpoint
T03 H3 Set point
T03 Output
T03 H3 Output
The system will not record any process data apart from these.
Alarm and event log
Data can only be transferred to ABB Service if the customer
removes the USB stick and sends the files to ABB for service
review. The customer has full control of the data and must allow
it to be transferred to ABB.
1
inserted into a USB slot

Checking the residual current circuit breaker

Introduction
Residual current circuit breakers disconnect the monitored
circuit from the remaining grid in the event
of a certain differential electric current. Test the residual current
circuit breaker at regular intervals in
order to simulate this error.
Maintenance interval
Every 6 months.
Illustration
The following diagram shows the location of the residual current
circuit breaker -5F3
1
in the control cabinet.
Requirements
The service switch is in the ON position; the gas sampling
probe is completely retracted from the kiln (see Operating
the service switch on page 100).
Tools required: Control cabinet key to open the control
cabinet
Instructions
Perform the following steps for residual current circuit breaker:
1. Open the control cabinet.
2. Press the test button "T"
breaker -5F3 to start the self-test (Picture: 2-pole residual
current circuit breaker for normal grid).
1
on the residual current circuit
105