Vertiv NetSure LMS1000 User Manual page 90

Lms data processing unit
Table of Contents

Advertisement

CHANNEL NUMBER
58214001 and 582126100
Only
Bnn51
through
Bnn74
582140001 and
582126100 Only
Bnn75
through
Bnn90
Bnn91
through
Bnn94
Viewing NPS Settings and Equipment Inventory: Use the command PRCONFIG NPS. This command is
available to a user with access to level 2 commands.
Changing the NPS Operating Mode (Float or Test/Equalize): Use the command SET NPS SYSTEM
TSTEQMODE. This command is available to a user with access to level 6 commands.
Toggling PCUs On or Off (TR Feature): Use the command SET NPS PCU. This command is available to a
user with access to level 6 commands.
Setting NPS Relay Test Time Period: Use the command SET NPS SYSTEM RLYTSTTIME. This command is
available to a user with access to level 5 commands.
Setting NPS Relay Test On: Use the command SET NPS SYSTEM RLYONTEST. This command is available
to a user with access to level 6 commands.
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
PCU nn-ssssssssss Alarm
through
PCU nn-ssssssssss Alarm
Alarm Log Sub-ID Entries
Bnnxx.07 Firmware Error
Bnnxx.09 Sense Loss (MN)
Bnnxx.10 Communications Fail (MJ)
Bnnxx.11 AC Line Low (MJ)
Bnnxx.13 Switched Off (MJ)
Bnnxx.14 Emergency Stop Active (MJ)
Bnnxx.15 High Ambient Temperature (MN)
Bnnxx.16 Converter Fail (MJ)
Bnnxx.17 Breaker Off (MJ)
Bnnxx.18 Output Inhibited (MJ)
Bnnxx.19 Fan Fail Major (MJ)
Bnnxx.21 Processor Fail (MJ)
Bnnxx.23 AC Line Too High (MJ)
Bnnxx.24 Fan Fail Minor (MN)
Bnnxx.25 AC Line Phase Lost (MJ)
Bnnxx.26 Power Factor Fail (MJ)
Bnnxx.27 Thermal Shutdown (MJ)
Bnnxx.28 Thermal Current Limit (MJ)
Bnnxx.30 Converter Unbalanced (MJ)
nn = Bay Number
xx = PCU element channel number
reserved
I/O Board bb-ss Binary #n (bb = NPS Bay #, ss = NPS Bay Slot #, n = corresponding
Binary Input #)
CHANNEL NAME
90

Advertisement

Table of Contents
loading

This manual is also suitable for:

586505000586505500

Table of Contents