Set Nps System Tsteqvolt - Vertiv NetSure LMS1000 User Manual

Lms data processing unit
Table of Contents

Advertisement

SET NPS SYSTEM TSTEQVOLT

Description: Sets the NPS "test/equalize output voltage" value.
Command Level: 6
Syntax:
SET NPS SYSTEM TSTEQVOLT
SE NP SY TST
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The MCA does not allow an adjustment which could result in a service interruption. Refer to the NPS
instruction manual's test/equalize adjustment procedure for details.
The following message is displayed if the setting was not accepted by the MCA.
Not Changed!
Related Commands: none
Example:
Command<6>: set NPS sys tst
Test/Equalize Voltage: 52.00 VDC
Test/Equalize Voltage: 52.1
New Test/Equalize Voltage Accepted.
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
326

Advertisement

Table of Contents
loading

This manual is also suitable for:

586505000586505500

Table of Contents