Vertiv NetSure LMS1000 User Manual page 493

Lms data processing unit
Table of Contents

Advertisement

RETRIEVE-THRESHOLD
(RTRV-TH-{EQPT|ALL})
Referenced In: TR-NWT-000833, Issue 5; pg. 4-337
General Description: Instructs LMS1000 to send the current threshold level (alarm limits) of one or more
monitored parameters for which violation will trigger an automatic message.
These threshold levels may apply to one or more equipment units, facilities, etc. within LMS1000.
Related Commands: SET-THRESHOLD
LMS1000 Access Level: 2
An error response with the error code PICC is returned if this command is entered by a valid user whose level of
access is less than the access level of this command.
LMS1000 Equivalent: LIMITS <t<n>>
LMS1000 Input Format Variations:
<aid>
The access identifier (<aid>) parameter identifies the equipment for which threshold levels are being retrieved.
Specifying a value of ALL requests retrieval of thresholds for all access identifiers of the type defined by the
command code modifier. If the command code modifier is ALL, the value of the access identifier parameter
should be ALL. A NULL value is not permitted for this parameter. Invalid values received for this parameter
return an error response with the error code IIAC.
<montype>
The monitor type (<montype>) parameter identifies the particular monitored parameter for which the threshold
is being retrieved. Values are derived from the MONITOR TYPE attribute of the LMS1000 analog or function
channel configuration. This parameter may contain a suffix to designate the type of threshold to be retrieved.
The suffix is separated from the monitor type parameter by a hyphen and takes the form LT or HT to indicate
low or high threshold types, respectively.
Example: DCVOLT-LT
A NULL value implies that threshold levels for all applicable monitored parameters are requested. Valid values
for this parameter can only contain alpha characters. Invalid values received for this parameter return an error
response with the error code IDNV.
<locn>
A NULL value is the only valid value for this parameter. Invalid values received for this parameter return an
error response with the error code INUP.
<tmper>
This parameter does not apply to LMS1000. The only valid value for this parameter is NULL. Invalid values
received for this parameter return an error response with the error code IDNV.
LMS1000 Response Format Variations: If no threshold can be found which matches the input parameters, an
error response with the error code IDNV is returned.
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
493