Command Level: 1
Syntax:
ALARMS [channel_type] [channel_designator] [channel_range] [node_designator] [node_range]
[group_designator] [search_text]
A [channel_type] [channel_designator] [channel_range] [node_designator] [node_range]
[group_designator] [search_text]
Comments: Analog and function channel alarm information includes the present value, the unit of measure,
and which alarm setpoint has been exceeded. Each type of alarm can be viewed separately by entering the
command ALARMS [node_designator] [node_range] followed by a space and then the character A for analog, B
for binary, R for relay, L for LED, F for function, G for group, or U for user.
Notes: Analog and binary channels are automatically mapped to MCA parameters when the VPS/NPS MCA
Interface is used. Alarm information for these analog and binary channels can be viewed using the ALARMS
command and options. Refer to Table 1 through Table 3 for a correlation between channels and mapped
VPS/NPS MCA and NPS MCA parameters. To view alarm information of just the VPS/NPS, use the ALARMS
NETSURE (ALARMS N) command and options.
Related Commands: ALARMS NETSURE
Example:
Command<1>: ALARMS
SYSTEM HARDWARE ALARMS:
I/O Network Failure
Unexpected Response received from node 02
Unable to communicate to node 03
Unrecognized node assembly found
Unexpected reset on node 05
Configuration mismatch on node 06
Assembly mismatch on node 07
Hardware mismatch on node 08
I/O card 01 on node 09 failed
Analog channel 1008 configuration failure
I/O card 02 on Main chassis failed
I/O card 03 on Main chassis does not match recorded the type
I/O card 07 on Main chassis is not a recognized type
ANALOG CHANNEL ACTIVE ALARMS AS OF 11:24:16 ON 01/01/01.
Chan
Description
A0001.2L Analog Channel 1
BINARY CHANNEL ACTIVE ALARMS AS OF 11:24:18 ON 01/01/01.
Chan
Description
B0001
Binary Channel 1
RELAY CHANNEL ACTIVE ALARMS AS OF 11:24:20 ON 01/01/01.
Chan
Description
R0001
Relay Channel 1
BINARY CHANNEL ACTIVE ALARMS AS OF 13:45:44 ON 05/13/96.
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
Value
Units
Alarm Limit
+20.3
Amps
20.0 H - Hi Limit 2
Status
Alarm Status / Class
CO
active
Status
Alarm Status / Class
On ,Pg
active
and
Class
MAJOR
MINOR
MINOR