This is the date when the triggering event occurred (i.e., the threshold was crossed). The format for this
parameter is MOY-DOM (Month-Of-Year - Day-Of-Month). MOY ranges from 1 to 12, and DOM ranges from 1 to
31. A null value for this parameter defaults to the date in the message header.
<ocrtm>
This is the time when the triggering event occurred. The format for this parameter is HOD-MOH-SOM (Hour-
Of-Day - Minute-Of-Hour - Second-Of-Minute). HOD ranges from 0 to 23. MOH and SOM range from 0 to 59.
A null value for this parameter defaults to the time in the message header.
<locn>, <dirn>
These parameters do not apply in LMS1000. A NULL value is inserted for them.
<monval>
This is the measured value of the monitored value associated with the alarm condition. A NULL value is
inserted if there is no measured value associated with this trouble. Parameter grouping cannot be used with
this parameter.
<thlev>
This is the value of the threshold level if the condition type parameter is a threshold violation. A NULL value
means there is no threshold level associated with the alarm condition. Parameter grouping cannot be used with
this parameter.
<tmper>
This is the accumulation time period for Performance Monitoring (PM) parameters. It represents the length of
time the alarm condition has been active. Parameter grouping cannot be used with this parameter. The format
for this parameter is VAL-UN, where valid values for VAL (value) and UN (unit) are:
VAL (value)
UN (unit)
1
DAY (day)
1 to 24
HR (hour)
1 to 1440
MIN (minute)
<conddescr>
This parameter is a text message which provides a detailed description of the alarm, event, or condition. It is an
ASCII string enclosed within a pair of escaped quotes (\"). It may also be used to describe any action to be
taken as a result of the condition. For this application, values are derived from the CONDITION DESCRIPTION
parameter of the LMS1000 channel or limit configuration with which the alarm condition is associated. If the
channel or limit parameter has not been configured, a NULL will be inserted for this parameter.
<aiddet>, <obsdbhvr>, <exptdbhvr>, <dgntype>, <tblistl>
These parameters do not apply or are not implemented in LMS1000. A NULL value is inserted for them.