VOLTAGE IS LOW
Condition Description:
Limit 4 Enabled: Yes
Limit 4 Enabled (Y or N):
Limit 4 Value: 40.0
Limit 4 Value:
Limit 4 Type: L
Limit 4 Type is High or Low (H or L):
Limit 4 Name: LVA2
Limit 4 Name:
Limit 4 Notification Code: CR
Limit 4 Notification Code:
Limit 4 Service Effect Code: NSA
Limit 4 Service Effect Code:
Limit 4 Alarm Class Number: 0
Condition Type: TOOLOW
Condition Type:
Limit 4 Condition Description:
VOLTAGE IS TOO LOW
Condition Description:
___________________________________________________________________________________
Command<6>: SET LIMITS F0001
FUNCTION CHANNEL 1 ALARM LIMITS AS OF 20:35:52 ON 02/09/01.
Chan
Description
F0001 Function Channel 1
Limit /
Name
5000.H
ABOVE 5000
Condition Description
CURRENT IS TOO HIGH
4000.H
ABOVE 4000
Condition Description
CURRENT IS HIGH
100.0L
BELOW 100
Condition Description
CURRENT IS LOW
50.00L
BELOW 50
Condition Description
CURRENT IS TOO LOW
Limit 1 Enabled: Yes
Limit 1 Enabled (Y or N):
Limit 1 Value: 5000.
Limit 1 Value:
Limit 1 Type: H
Limit 1 Type is High or Low (H or L):
Limit 1 Name: ABOVE 5000
Limit 1 Name:
Limit 1 Notification Code: CR
Limit 1 Notification Code:
Limit 1 Service Effect Code: SA
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
Class
Condtype
TOOHIGH
HIGH
LOW
TOOLOW
Ntfc
Svef
CR
SA
CR
SA
CR
SA
CR
SA
283