Vertiv NetSure LMS1000 User Manual page 163

Lms data processing unit
Table of Contents

Advertisement

See Operating LMS1000 for a description and examples of the Polarity and Alarm Limit Mode attributes.
Analog channel configuration error messages:
WARNING, no hardware exists for this channel!
(unmapped node #, no I/O card exists)
Node is failed, channel hardware not configured!
(node failure)
Channel hardware configuration error!
(bad I/O card)
Related Commands: none
Example:
Command<5>: CONFIG
Which channel? A0001
ANALOG CHANNEL CONFIGURATION AS OF 07:35:50 ON 01/01/01.
Chan
Description
A0001 Analog Channel 1
Sub-access ID
ANALOG1
A0001 Analog Channel 0001
LIMITS CONFIGURATION
Limit /
Name
70.0 H
HVA2
Condition Description
THIS VOLTAGE IS TOO HIGH
60.0 H
HVA1
Condition Description
THIS VOLTAGE IS HIGH
50.0 L
LVA1
Condition Description
THIS VOLTAGE IS LOW
40.0 L
LVA2
Condition Description
THIS VOLTAGE IS TOO LOW
Channel active (Y or N): Y
Name: Analog Channel 1
Name: MAIN SHUNT
Sub-access Identifier: ANALOG1
Sub-access Identifier: RECT1
System Alarm Report mode: Y
System Alarm Report mode (Y or N):
Transducer Type:
Transducer Type (Shunt, Current, Voltage, Temp, or None):
Shunt type: current info
Shunt type (50mv or 100mv):
Scale Factor: 100.0
Scale Factor:
Monitor type: DCVOLTS
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
Act Rpt Pol Scale 4-20 Unit Off-Dly-On
Y
Y
+
Montype
Monfmt
DCVOLTS
D
-- Limits mode: Normal
Class
Condtype
MAJOR
TOOHIGH
MAJOR
HIGH
MINOR
LOW
MINOR
TOOLOW
100.0
N
Volt
0
Ntfc
Svef
MJ
SA
MJ
SA
MN
NSA
MN
NSA
0
163