Vertiv NetSure LMS1000 User Manual page 467

Lms data processing unit
Table of Contents

Advertisement

INITIALIZE-REGISTER
(INIT-REG-{EQPT|ALL})
Referenced In: TR-NWT-000833, Issue 5, pg. 4-139
General Description: Instructs LMS1000 to initialize to a specific value one or more storage registers or event
counters associated with one or more equipment units, facilities, etc. within LMS1000.
In most common instances, these registers contain performance monitoring information.
An entry is made in the LMS1000's event log indicating this command was executed by the current sessions
user. The event description indicates that the statistics were cleared.
Related Commands: None
LMS1000 Access Level: 6
An error response with the error code PICC is returned if this command is entered by a valid user whose level of
access is less than the access level of this command.
LMS1000 Equivalent: CLR STATS <t<n>>
LMS1000 Input Format Variations: The command code modifier COM is not supported by LMS1000.
<aid>
Specifying a value of ALL for the access identifier (<aid>) parameter initializes all registers for all access
identifiers of the type defined by the command code modifier. If the command code modifier is ALL, the value
of the access identifier parameter must be ALL. A NULL value is not permitted for this parameter. Invalid
values received for this parameter return an error response with the error code IIAC.
<montype>
This parameter is not supported by LMS1000. The only valid value for this parameter is ALL. Invalid values
received for this parameter return an error response with the error code IDNV.
<monval>
This parameter is not supported by LMS1000. The only valid value for this parameter is NULL. Invalid values
received for this parameter return an error response with the error code IDNV.
<locn>
This parameter does not apply to LMS1000. The only valid value for this parameter is NULL. Invalid values
received for this parameter return an error response with the error code IDNV.
<dirn>
This parameter does not apply to LMS1000. The only valid value for this parameter is NULL. Invalid values
received for this parameter return an error response with the error code IDNV.
<tmper>
This is the accumulation time period for the Performance Monitoring (PM) information. This parameter is not
supported by LMS1000. The only valid value for this parameter is NULL. A NULL value causes the parameter
to default to 1-HR. Invalid values received for this parameter return an error response with the error code IDNV.