Vertiv NetSure LMS1000 User Manual page 528

Lms data processing unit
Table of Contents

Advertisement

NOTE!
re-edited to correct the appropriate program line. The CLR PROG command may be
used instead of re-editing the upload file. Refer to the CLR PROG command in the
COMMANDS section.
202 blocks received OK.
R01=h1
^
Program error -- Bad Character
Upload Complete.
Uploading the Configuration from a PC to the LMS1000 using TFTP
a)
Start a separate TFTP client session on the host from which the configuration file is transferred.
b)
Log onto the system using the default level six password (6).
c)
Enter the command
UPLOAD using TFTP
d)
After seeing the above prompt, start the upload process from the client. DO NOT ATTEMP THE
UPLOAD UNTIL THE PROMPT ABOVE IS DISPLAYED.
Configuring the Nodes
1.
Enter the NODE LIST command and verify all nodes that were previously present are still present.
NOTE!
Node numbers and names will NOT be the same as before. Verify the nodes using the neuron ID
and other node parameters.
2.
Enter the NODE CONFIG command and configure the node numbers and names using the information
recorded earlier.
Replacing an Expansion Cabinet CPU Circuit Card
NOTE!
Figure 5
Refer to
NOTE!
When performing any step in this procedure which requires removal of existing hardware, retain
all hardware for use in subsequent steps.
Procedure:
1.
Observe the admonishments presented at the beginning of this section, and in the previous section
titled "REPAIR AND REPLACEMENT INFORMATION".
2.
Remove DC input power from the LMS1000 CPU circuit card.
3.
586505000/586505500 LMS1000 Cabinet: Rotate the two captive fasteners on the front of the shelf
until the arrow on the fastener points up or down, and pivot the door open.
or
582140000/582140001/582126100 Power System: Open the bay's front door.
4.
Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
If an error message (as shown below) appears, the file being uploaded must be
UPLOAD TFTP
, then press
as this procedure is performed.
ENTER
. The following will be displayed.
528