Vertiv NetSure LMS1000 User Manual page 522

Lms data processing unit
Table of Contents

Advertisement

ERROR TYPE
(CHANNEL #)
Description: Unable to communicate with expansion cabinet or assembly.
Action: Determine the source node via the ALARMS and NODE LIST command. First,
Node
verify the node has power. Next, verify the echelon network connection. For Expansion
Communication
Cabinets, verify all installed I/O cards are recognized types for the version of firmware
Error
installed in the LMS1000. Refer to SAG586505000/SAG586505500 for valid card types.
(B0089)
The SAG can be accessed via the Electronic Documentation Package provided on the
CD shipped with your system.
Description: A node on the network has been reset by its watchdog supervisory circuit.
Node Watch Dog
Action: Note the occurrence in a record or log (such as an LMS1000 INFO page).
Reset Error
Replace node CPU circuit card in any node exhibiting this error more than one time in
(B0090)
any given six month period.
Description: Reported node configuration parameter does not match configuration
Node
stored on Master: Cabinet spec, Cabinet serial, Cabinet location, Point use flags,
Configuration
Distribution module number.
Mismatch
Action: Determine the source node via the ALARMS command. Execute the NODE
(B0091)
CONFIG command and verify the configuration stored is correct. Be sure to save
changes whether any made or not when prompted. Verify the nodes channels as well.
Description: Reported Assembly Number doesn't match information stored on Master
Node Assembly
node.
Mismatch
Action: Determine the source node via the ALARMS command. Execute the NODE
(B0092)
CONFIG command and verify the assembly number stored is correct. Be sure to save
changes whether any made or not when prompted. Verify the nodes channels as well.
Description: Hardware reported by node does not match information stored on Master
node: Number of boards, Board style, Number of point groups, Point type, Number of
Node H/W
points, Failure to get point group.
Mismatch
Action: Determine the source node via the ALARMS command. Verify the I/O circuit
(B0093)
cards in the node are the desired configuration. Enter the NODE INITIO command. Note
that the configuration for the channels on the source node may need re-configuring after
executing the NODE INITIO command.
Description: Expansion Cabinet: I/O card failure. All cards to the right of a failed or
missing card will be reported as failed.
Expansion Assembly: A/D Malfunction, Neuron Circuitry Failure.
Node I/O H/W
Action: Expansion Cabinet: Determine the source card via the ALARMS command.
Failure
Replace failed or missing cards with exact type.
(B0094)
Expansion Assembly: Replace the Expansion Assembly as described in the "Replacing an
Expansion Assembly Card" subsection of the "Troubleshooting and Repairing" section of
the manual.
Description: Reported configuration of universal A/D point does not match
Analog H/W
configuration stored in Network or Master Node I/O Subsystem.
Configuration
Action: Determine the source channel via the ALARMS command. Enter the CONFIG
Error
Axxxx command and verify the channel configuration is as desired. Be sure to save
(B0095)
changes even if none are made. Verify the error clears within 15 seconds.
Temperature
Description: Temperature probe sensor has failed.
Probe Failure
Action: Replace the temperature probe specified by the ALARMS command.
(B0096)
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
DESCRIPTION/ACTION
522