Vertiv NetSure LMS1000 User Manual page 105

Lms data processing unit
Table of Contents

Advertisement

• A value in parenthesis represents the continuous charge time (after a discharge); max display is F60.1
limit.
F60 & F59 – Predicted Reserve Capacity is set automatically (there is no control program):
• "N/A" displays when the battery is charging and before a valid prediction is available by the algorithm.
• When available, F60 is the sum of the elapsed discharge time plus the predicted remaining reserve time
(F61).
• When available, F59 is the value of F60 multiplied by the load current, with results in amp-hours.
• End-of-life alarm is limit #4 and defaults to 75% of limit #1; requires full recharge period beforehand to
alarm.
1
BOD is determined by an alarm as follows: B9902 for a NS702/80x; B9003 for NS701; F62.1 (limit 1) for a stand-alone LMS
2
IEEE-1188 Recommended Practice for Maintenance, Testing, and Replacement of VRLA Batteries for Stationary Applications
3
F59 limits default to zero and update during the highest prediction occurring within the first 6 months (of initial clock setup)
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
105