Setting the VPS/NPS Audible Alarm Cutoff Reset Time Period (NAG): Use the command SET NETSURE
SYSTEM NAGTIMER. This command is available to a user with access to level 4 commands.
Setting VPS/NPS Alarm Parameters: Use the commands SET NETSURE SYSTEM HIVLTALM1, SET
NETSURE SYSTEM HIVLTALM2, SET NETSURE SYSTEM BATONDISCH, SET NETSURE SYSTEM
50%BATONDISCH, SET NETSURE SYSTEM OVRCURRENT, SET NETSURE SUBSYSTEM HIVALM, SET
NETSURE SUBSYSTEM LVALM, SET NETSURE SUBSYSTEM OVRCURRENT, SET NETSURE SYSTEM
RLYTESTTIME, SET NETSURE SYSTEM TEMPHIGH, SET NETSURE SYSTEM TEMPLOW, and SET NETSURE
SYSTEM AUTOEQMULT. These commands are available to a user with access to level 5 commands.
Changing the Password Issued by LMS1000 to Gain Remote Access to the VPS/NPS: Use the command
SET NETSURE PASSWORD. This command is available to a user with access to level 6 commands.
Changing the VPS/NPS Operating Mode (Float or Test/Equalize): Use the command SET NETSURE
SYSTEM MODE. This command is available to a user with access to level 6 commands.
Setting VPS/NPS "System Voltage" Calibration: Use the command SET NETSURE SYSTEM CALVOLT.
This command is available to a user with access to level 6 commands.
Setting VPS/NPS "Subsystem Voltage" Calibration: Use the command SET NETSURE SUBSYSTEM
CALVOLT. This command is available to a user with access to level 6 commands.
Resetting VPS/NPS "System Voltage" Calibration to Factory Defaults: Use the command SET NETSURE
SYSTEM FACTORYCAL. This command is available to a user with access to level 6 commands.
Resetting VPS/NPS "Subsystem Voltage" Calibration to Factory Defaults: Use the command SET
NETSURE SUBSYSTEM FACTORYCAL. This command is available to a user with access to level 6 commands
Setting VPS/NPS Analog Battery Charge Temperature Compensation Module's Calibration Voltage: Use
the command SET NETSURE SYSTEM TEMPCOMP. This command is available to a user with access to level 6
commands.
Setting VPS/NPS Digital Battery Charge Temperature Compensation: Use the commands SET NETSURE
SYSTEM COMPSOURCE, SET NETSURE SYSTEM COMPSLOPE, SET NETSURE SYSTEM COMPMAX, and SET
NETSURE SYSTEM COMPMIN. This command is available to a user with access to level 6 commands.
Setting VPS/NPS Available PCU Mounting Positions: Use the commands SET NETSURE SYSTEM
25APLACES, SET NETSURE SYSTEM 50APLACES, SET NETSURE SYSTEM 100APLACES, and SET NETSURE
SYSTEM 200APLACES (you can also use the command SET NETSURE PCU TOTALSLOTS). These
commands are available to a user with access to level 6 commands.
Resetting VPS/NPS Inventory: Use the command SET NETSURE SYSTEM INVENTORY. This command is
available to a user with access to level 6 commands.
Setting VPS/NPS Float Output Voltage: Use the command SET NETSURE SYSTEM FLTVOLT. This
command is available to a user with access to level 6 commands.
Setting VPS/NPS Test/Equalize Output Voltage: Use the command SET NETSURE SYSTEM TSTEQVOLT.
This command is available to a user with access to level 6 commands.
Setting VPS/NPS High Voltage Shutdown: Use the command SET NETSURE SYSTEM HVS. This command
is available to a user with access to level 6 commands.
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA