RETRIEVE-ATTRIBUTE-ENVIRONMENT
(RTRV-ATTR-ENV)
Referenced In: TR-NWT-000833, Issue 5, pg. 4-237
General Description: Instructs LMS1000 to send the current attributes associated with the specified
environmental alarm.
Related Commands: SET-ATTRIBUTE-ENVIRONMENT
LMS1000 Access Level: 2
An error response with the error code PICC is returned if this command is entered by a valid user whose level of
access is less than the access level of this command.
LMS1000 Equivalent: None
LMS1000 Input Format Variations:
<aid>
The access identifier (<aid>) parameter identifies equipment associated with the environmental alarm being
requested. Entering a value of ALL requests retrieval of all environmental alarms specified by the notification
code (<ntfcncde>) parameter and alarm type (<almtype>) parameter. A NULL value is not permitted for this
parameter. Invalid values received for this parameter return an error response with the error code IIAC.
<ntfcncde>
Specifies the notification code parameter associated with the environmental alarm conditions being retrieved.
This parameter is an attribute of the LMS1000 channel or limit configuration.
Valid values for this parameter are as follows:
CR
critical alarm
MJ
major alarm
MN
minor alarm
NULL
request retrieval of attributes for environmental alarms for all of the above codes
Invalid values for this parameter return an error response with the error code IDNV.
<almtype>
Specifies the alarm type parameter associated with the environmental alarms being retrieved. Specifying a
NULL value requests retrieval of all types of environmental alarms. Values are derived from the CONDITION
TYPE attribute of the LMS1000 channel or limit configuration with which the alarm is associated. The error
code for an invalid value for this parameter is IDNV.
LMS1000 Response Format Variations:
<ntfcncde>
This is the notification code parameter associated with the environmental alarm given in this block. Valid
values are the same as for the input format. Values are derived from the NOTIFICATION CODE attribute of the
LMS1000 channel or limit configuration with which the alarm condition is associated.
<almtype>