Limit 2 Notification Code:
Limit 2 Service Effect Code: SA
Limit 2 Service Effect Code:
Limit 2 Alarm Class Number: 1
Limit 3 Enabled: Yes
Limit 3 Enabled (Y or N):
Limit 3 Value: 50.00
Limit 3 Value: 500
Limit 3 Type: L
Limit 3 Type is High or Low (H or L):
Limit 3 Name: LVA1
Limit 3 Name: BELOW 500
Limit 3 Notification Code: MN
Limit 3 Notification Code:
Limit 3 Service Effect Code: NSA
Limit 3 Service Effect Code:
Limit 3 Alarm Class Number: 2
Condition Type: LOW
Condition Type:
Limit 3 Condition Description:
THIS VOLTAGE IS LOW
Condition Description:
THIS CURRENT IS LOW
Limit 4 Enabled: Yes
Limit 4 Enabled (Y or N):
Limit 4 Value: 40.00
Limit 4 Value: 100
Limit 4 Type: L
Limit 4 Type is High or Low (H or L):
Limit 4 Name: LVA2
Limit 4 Name: BELOW 100
Limit 4 Notification Code: MN
Limit 4 Notification Code:
Limit 4 Service Effect Code: NSA
Limit 4 Service Effect Code:
Limit 4 Alarm Class Number: 2
Condition Type: TOOLOW
Condition Type:
Limit 4 Condition Description:
THIS VOLTAGE IS TOO LOW
Condition Description:
THIS CURRENT IS TOO LOW
Unit Text: VOLT
Unit Text: AMPS
Off Delay Time: 0s
Off Delay Time:
On Delay Time: 0s
On Delay Time: 15
Save changes (Y or N): Y
Enter Program Line:
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
167