Vertiv NetSure LMS1000 User Manual page 472

Lms data processing unit
Table of Contents

Advertisement

OPERATE-EXTERNAL-CONTROL
(OPR-EXT-CONT)
Referenced In: TR-NWT-000833, Issue 5, pg. 4-153
General Description: Instructs LMS1000 to activate a specified relay channel to operate an external control.
Momentary operation of the external control is not implemented in LMS1000.
An entry is made in the LMS1000's event log indicating this command was executed by the current sessions
user.
Related Commands: RELEASE-EXTERNAL-CONTROL, RETRIEVE-EXTERNAL-CONTROL
LMS1000 Access Level: 5
An error response with the error code PICC is returned if this command is entered by a valid user whose level of
access is less than the access level of this command.
LMS1000 Equivalent: SET RLY
LMS1000 Input Format Variations:
<aid>
Specifying a value of ALL for the access identifier (<aid>) parameter requests the activation of all LMS1000
relay channels specified by the control type (<conttype>) parameter. A NULL value is not permitted for this
parameter. Invalid values received for this parameter return an error response with the error code IIAC.
<conttype>
The control type (<conttype>) parameter is an attribute of the LMS1000 relay channel configuration. A NULL
value requests activation of all LMS1000 relay channels identified by the access identifier (<aid>) parameter.
When the access identifier (<aid>) parameter is ALL, the control type (<conttype>) parameter should not be
NULL. Invalid values received for this parameter return an error response with the error code IDNV.
<dur>
This is the duration for which the external control is to be operated. Parameter grouping cannot be used with
this parameter.
Valid values for the <dur> parameter are as follows:
CONTSContinuous
LMS1000 does not support the value of MNTRY for this parameter. If the value MNTRY is received, an error
response with the error code INUP is returned. Other invalid values received for this parameter return an error
response with the error code IDNV. A NULL value for this parameter is not allowed. If a NULL value is received
for this parameter, an error response with the error code IDNV is returned.
LMS1000 Response Format Variations: None