<locn>
This parameter does not apply to LMS1000. The only valid value for this parameter is NULL. Invalid values
received for this parameter return an error response with the error code IDNV.
<dirn>
This parameter does not apply to LMS1000. The only valid value for this parameter is NULL. Invalid values
received for this parameter return an error response with the error code IDNV.
<tmper>
This parameter does not apply to LMS1000. The only valid value for this parameter is NULL. Invalid values
received for this parameter return an error response with the error code INUP.
LMS1000 Response Format Variations:
<aidtype>
Valid values for an access identifier type response parameter are:
EQPT
equipment
COM
common
<ntfcncde>
This is the notification code parameter associated with a single alarm condition given in this block. Valid values
are the same as for the input format. Values are derived from the NOTIFICATION CODE attribute of the
LMS1000 channel or limit configuration with which the alarm condition is associated.
<condtype>
This is the condition type parameter of the alarm condition being given in this block. Values are derived from
the CONDITION TYPE attribute of the LMS1000 channel or limit configuration with which the alarm condition is
associated.
<srveff>
This is the service effect parameter associated with a single alarm condition given in this block. Valid values are
the same as for the input format. Values are derived from the SERVICE EFFECT CODE attribute of the
LMS1000 channel or limit configuration with which the alarm condition is associated.
<ocrdat>
This is the date when the triggering event occurred. The format for this parameter is MOY-DOM (Month-Of-
Year - Day-Of-Month). MOY ranges from 1 to 12, and DOM ranges from 1 to 31. A NULL value for this
parameter defaults to the current date unless the <ocrtm> parameter is NULL, then this parameter does not
apply.
<ocrtm>
This is the time when the triggering event occurred. The format for this parameter is HOD-MOH-SOM (Hour-
Of-Day - Minute-Of-Hour - Second-Of-Minute). HOD ranges from 0 to 23. MOH and SOM range from 0 to 59.
A NULL value means this parameter and the <ocrdat> parameter are not applicable.