RETRIEVE-CONDITION
(RTRV-COND-{EQPT|ALL})
Referenced In: TR-NWT-000833, Issue 5, pg. 4-257
General Description: Instructs LMS1000 to send the current state and standing condition (alarm or status)
associated with one or more equipment units, facilities, etc. within LMS1000.
In addition, it may be used to summarize the status of the LMS1000 by providing entity states.
Related Messages: REPORT CONDITION EQUIPMENT
LMS1000 Access Level: 1
LMS1000 Equivalent: None
LMS1000 Input Format Variations: The command code modifier COM is not supported.
<aid>
Specifying a value of ALL for the access identifier (<aid>) parameter requests retrieval of conditions for all
access identifiers of the type defined by the command code modifier. Use of the command code modifier ALL
results in retrieval of all conditions in the LMS1000. If the command code modifier is ALL, the value of the
access identifier must be ALL. A NULL value is not permitted for this parameter. Invalid values received for
this parameter return an error response with the error code IIAC.
<typereq>
Specifies the type of condition or state to be retrieved. A valid value can be any condition type (<condtype>)
parameter. Values are derived from the CONDITION TYPE attribute of the LMS1000 channel or limit
configuration with which the alarm condition is associated. A NULL value causes all condition types to be
retrieved. Invalid values for this parameter return an error response with the error code IDNV.
<locn>
This parameter does not apply to LMS1000. The only valid value for this parameter is NULL. Invalid values for
this parameter return an error response with the error code INUP.
<dirn>
This parameter does not apply to LMS1000. The only valid value for this parameter is NULL. Invalid values for
this parameter return an error response with the error code INUP.
<tmper>
This parameter does not apply to LMS1000. The only valid value for this parameter is NULL. Invalid values for
this parameter return an error response with the error code INUP.
LMS1000 Response Format Variations:
<aidtype>
Valid values for an access identifier type response parameter are:
EQPT
equipment
COM
common