Vertiv NetSure LMS1000 User Manual page 461

Lms data processing unit
Table of Contents

Advertisement

EDIT-USER-SECURITY
(ED-USER-SECU)
Referenced In: TR-NWT-000835, Issue 3, pg. 3-59
General Description: Edits the user identifier (<uid>) parameter (i.e., LMS1000 user name), privilege identifier
(<pid>) parameter (i.e., LMS1000 user password), calling identifier (<cid>) parameter (i.e., LMS1000 user primary
phone number), and user access privilege (<uap>) parameter (i.e., LMS1000 user access level) of the specified
user.
When executed, the command sets the NAME, PASSWORD, PRIMARY PHONE, and ACCESS LEVEL attributes
of the specified user's LMS1000 user configuration to the new values.
An entry is made in the LMS1000's event log indicating this command was executed by the current sessions
user. The event description indicates that the specified user's LMS1000 user parameters were edited.
Related Commands: None
LMS1000 Access Level: 6
An error response with the error code PICC is returned if this command is entered by a valid user whose level of
access is less than the access level of this command.
LMS1000 Equivalent: None
LMS1000 Input Format Variations:
<aid>
The access identifier (<aid>) parameter is the same value as the user identifier (<uid>) parameter for the user
whose parameters are being edited. Invalid values received for this parameter return an error response with the
error code IIAC.
<uid>
The user identifier (<uid>) parameter determines the new user identifier which replaces the current one. This
parameter is the new NAME attribute for the specified user's LMS1000 user configuration. Invalid values
received for this parameter return an error response with the error code IDNV. If the entered value for this
parameter matches an existing user identifier for another user, an error response with the error code PIUI is
returned.
<pid>
The privilege identifier (<pid>) parameter determines the new privilege identifier which replaces the current
one. This parameter is the new PASSWORD attribute for the specified user's LMS1000 user configuration. The
LMS1000 allows a maximum of eight characters for a password. At least two characters must be non-alpha,
and at least one character must be a symbol. (Valid symbols are the '#', '%', and '+' characters.) Invalid values
received for this parameter return an error response with the error code IDNV. If the entered value for this
parameter matches an existing privilege identifier for another user, an error response with the error code PIUI is
returned.
<cid>
The calling identifier (<cid>) parameter determines the new calling identifier which replaces the current one.
This parameter is the new PRIMARY PHONE attribute for the specified user's LMS1000 user configuration. It
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
461