SET NETSURE SYSTEM TEMPLOW
Description: Sets the VPS/NPS "low temperature alarm" values.
Command Level: 5
Syntax:
SET NETSURE SYSTEM TEMPLOW<n>
SE N SY TEMPL<n>
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The following message is displayed if the setting was not accepted by the MCA:
Power system did not accept the new value, setting remains unchanged.
Related Commands: none
Example:
Command<5>: SET NETSURE SYSTEM TEMPLOW
Which Temperature Probe (1-8)?
Temperature Probe #1 not installed
Command<5>: SET NETSURE SYSTEM TEMPLOW 1
Temperature Probe #1 not installed
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA