NOTE!
A fully configured system downloaded over a phone line at 1200 bits/s may require up to 15
minutes.
NOTE!
The communications parameters of the remote terminal must match the system's default
parameters. The default parameters are 8 data bits, 1 stop bit, and no parity. These defaults cannot be
changed.
a)
Log on to the system. The user must have access to level 6 commands.
b)
Enter the command DOWNLOAD, then press ENTER. You have up to 1 minute to initiate a file
transfer.
c)
The system will wait up to 1 minute before aborting the process if no file transfer occurs. The
system waits for a 'C' character, which is the synchronization character for starting an XMODEM
CRC file transfer.
d)
At the PC, initiate a file transfer using XMODEM CRC protocol.
Downloading the Configuration from the LMS1000 to a PC using TFTP
a)
Start a separate TFTP client session on the host to which the configuration file is transferred.
b)
Log on to the system. The user must have access to level 6 commands.
c)
Enter the command
d)
DOWNLOAD using TFTP
After seeing the above prompt, start the download process from the client. DO NOT ATTEMP THE
e)
DOWNLOAD UNTIL THE PROMPT ABOVE IS DISPLAYED.
Save the Node Configuration
1.
Enter the command NODE LIST, and copy the displayed information. This information is currently not
saved when the configuration is downloaded using the DOWNLOAD command. This information has to
be manually re-entered after replacing the CPU card.
Replace the CPU Circuit Card
1.
Remove DC input power from the LMS1000 CPU circuit card.
2.
586505000/586505500 LMS1000 Cabinet: Rotate the two captive fasteners on the front of the shelf
until the arrow on the fastener points up or down, and pivot the door open.
or
582140000/582140001/582126100 Power System: Open the bay's front door.
3.
Connect an approved grounding strap to your wrist. Attach the other end to a suitable ground.
4.
If external CPU/hardware fail alarms are connected to J4 on the circuit card, gently remove the top half
of connector J4 from the bottom half located on the existing CPU circuit card.
5.
Remove the CPU circuit card by loosening the retaining screw. In a 582140000/582140001/582126100
Power System, note that if a modem is installed, it also contains a bracket with a retaining screw.
Remove the modem cable, if present.
6.
Remove the modem circuit card, if present.