Vertiv NetSure LMS1000 User Manual page 233

Lms data processing unit
Table of Contents

Advertisement

A0001 Analog Channel 1
Sub-access ID
ANALOG1
LIMITS CONFIGURATION
Limit /
Name
70.0 H
HVA2
Condition Description
VOLTAGE IS TOO HIGH
60.0 H
HVA1
Condition Description
VOLTAGE IS HIGH
50.0 L
LVA1
Condition Description
VOLTAGE IS LOW
40.0 L
LVA2
Condition Description
VOLTAGE IS TOO LOW
___________________________________________________________________________________
Command<2>: PRCONFIG A9065
ANALOG CHANNEL CONFIGURATION AS OF 11:13:06 ON 02/02/01.
Chan
Description
A9065
NETSURE System Voltage
Sub-access ID
___________________________________________________________________________________
Command<2>:
PRCONFIG B65
BINARY CHANNEL CONFIGURATION AS OF 11:16:14 ON 02/02/01.
Chan
Description
B9065 NETSURE System High Voltage 1
Sub-access ID
Condition Description
___________________________________________________________________________________
Command<2>: P E1
ENERGY MANAGEMENT CHANNEL CONFIGURATION AS OF 16:33:32 ON 09/11/01.
Chan
Description
E0001 Energy Mngmt PCU1
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
Y
Y
+
Montype
Monfmt
DCVOLTS
D
Class
Condtype
MAJOR
TOOHIGH
MAJOR
HIGH
MINOR
LOW
MINOR
TOOLOW
Act Rpt Pol Scale 4-20 Unit Off-Dly-On
Y
N
+
Montype
Monfmt
I
Act Rpt Cont Class Off-Dly-On
Y
Condtype
Act Capacity
Y
100.0
N
Amps
0s
Ntfc
Svef
MJ
SA
MJ
SA
MN
NSA
MN
NSA
---
--
VDC
---
N
--
0s
Ntfc
Svef
CR
SA
Sht RFA TR
Dsl
100.0
A70 B84 ---
Y
0s
---
0s
233