Vertiv NetSure LMS1000 User Manual page 354

Lms data processing unit
Table of Contents

Advertisement

Report Device: Modem
Report Device (Modem, Ethernet, X25, or Telnet):
Report Mode: Off
Report Mode (Off, E-mail, TL1):
Report Retry Time: 15
Report Retry Time:
TL1 Report Condition interval: 0
TL1 Report Condition interval:
Save changes (Y or N):
Edit User Channels (Y or N):
Enter channel (eg. A0012 or A0001-0006) or D to display.
Add Channel:
Enter channel (eg. A0012 or A0001-0006) or D to display.
Del Channel:
SET VI
Description:
Sets the channels that the Web Interface uses to display system voltage and
system current.
Command Level:
5
Syntax:
SET VI
SE VI
Comments:
One at a time, the current setting is displayed and then a line to change the
setting.
Simply press enter to keep the current setting.
Notes:
The Plant Voltage and Plant Current channels default to settings shown below.
NetSure 702/801/802: Voltage channel - A9901 ;
NetSure 701/VPS: Voltage channel - A9001 ;
Stand-alone: Voltage channel - none ;
Related Commands:
none
Example:
Command<6>: SET VI
Plant Voltage:
Plant Voltage:
A9001
Plant Current:
Plant Current:
A9002
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
y
y
Current channel - A9002
Current channel - none
Current channel - A9903
354