Vertiv NetSure LMS1000 User Manual page 405

Lms data processing unit
Table of Contents

Advertisement

STATS DAILY
Description: Displays the Daily Advanced Statistics for analog and function channels set for Advanced
Statistics.
Command Level: 1
Syntax:
STATS DAILY [USER | group_designator] [CSV]
Comments: Information presented includes the daily peak maximum, peak minimum, and hour-average values.
Entering the command modifier USER displays statistics for only analog and function channels that are set for
Advanced Statistics and are also part of the current User's channel group.
Entering the command modifier group_designator displays statistics for only analog and function channels that
are set for Advanced Statistics and are also in that group. The group designator must be entered in the form
'G<n>', where 'n' is a number 1-8.
Entering the command modifier CSV displays the statistics in the "comma separated value" format. This allows
the data to be imported into a spreadsheet.
Notes: A system reset has no effect on the collection and processing of daily statistical data except as it
affects the calculations of the minute and hour averages used. A reset causes calculations for these values to
be restarted. Thus, the hour averages will include data calculations using values collected from the time of the
reset through the end of the hour. Data calculations for the hour using values collected prior to the reset are
lost.
A system reset after a change in date (i.e., system was powered down during a period when the date changed)
does not affect the collection and processing of the hour-average data except for a change in the date portion
of the time/date stamp. A change in date affects the collection of daily statistical data in the following manner.
• Statistical comparisons for the present day (old date) are completed and collection of statistical data for
the new day (date) is started.
A change in time affects the collection and processing of daily and weekly statistical data only as the number of
time periods (hours, minutes) in which data is be collected may be greater or less than normal. A change in
time affects the collection and processing of the hour-average data in the following manner.
• Calculations for the present hour (old time) are completed and the data is stamped with a date and time
of the new time less one hour (e.g., time was changed from 14:34 to 11:42 , the timestamp is 10:42).
• Calculations are started for the present hour (of the new time) and are completed at the end of the hour.
The time/date stamp is the new hour.
Related Commands: STATS, STATS WEEKLY, STATS CHANNELS, SET STATS CHANNELS, CLR STATS,
CLR STATS DAILY, CLR STATS WEEKLY
Example:
Command<1>: stats daily
DAILY STATISTICS
10/25/2005 - Tuesday
CHAN
----------------------------------------------------------------------------
MAXIMUM PEAK A9001 System Voltage – Fifth Flr Plt 52.08 VDC
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
DESCRIPTION
VALUE
MEAS
DATE/TIME
09/22/05 14:17:20
405

Advertisement

Table of Contents
loading

This manual is also suitable for:

586505000586505500

Table of Contents