Vertiv NetSure LMS1000 User Manual page 398

Lms data processing unit
Table of Contents

Advertisement

SET NETSURE SYSTEM TEMPHIGH
Description: Sets the VPS/NPS "high temperature alarm" values.
Command Level: 5
Syntax:
SET NETSURE SYSTEM TEMPHIGH<n>
SE N SY TEMPH<n>
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The following message is displayed if the setting was not accepted by the MCA:
Power system did not accept the new value, setting remains unchanged.
Related Commands: none
Example:
Command<5>: SET NETSURE SYSTEM TEMPHIGH
Which Temperature Probe (1-8)? 1
Temperature Probe #1 not installed
Command<5>: SET NETSURE SYSTEM TEMPHIGH 1
Temperature Probe #1 not installed
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
398

Advertisement

Table of Contents
loading

This manual is also suitable for:

586505000586505500

Table of Contents