Vertiv NetSure LMS1000 User Manual page 166

Lms data processing unit
Table of Contents

Advertisement

Condition Description
THIS VOLTAGE IS TOO HIGH
60.00H
HVA1
Condition Description
THIS VOLTAGE IS HIGH
50.00L
LVA1
Condition Description
THIS VOLTAGE IS LOW
40.00L
LVA2
Condition Description
THIS VOLTAGE IS TOO LOW
Channel active (Y or N): Y
Name: Function Channel 1
Name:
Sub-access Identifier: FUNCTION1
Sub-access Identifier:
System Alarm Report mode: Y
System Alarm Report mode (Y or N):
Monitor type: DCVOLTS
Monitor type: DCAMPS
Monitor Value Format: Decimal
Set monitor value format to integer(I) or decimal(D): I
Limit 1 Enabled: Yes
Limit 1 Enabled (Y or N):
Limit 1 Value: 70.00
Limit 1 Value: 5000
Limit 1 Type: H
Limit 1 Type is High or Low (H or L):
Limit 1 Name: HVA2
Limit 1 Name: ABOVE 5000
Limit 1 Notification Code: MJ
Limit 1 Notification Code:
Limit 1 Service Effect Code: SA
Limit 1 Service Effect Code:
Limit 1 Alarm Class Number: 1
Condition Type: TOOHIGH
Condition Type:
Limit 1 Condition Description:
THIS VOLTAGE IS TOO HIGH
Condition Description:
THIS CURRENT IS TOO HIGH
Limit 2 Enabled: Yes
Limit 2 Enabled (Y or N):
Limit 2 Value: 60.00
Limit 2 Value: 4200
Limit 2 Type: H
Limit 2 Type is High or Low (H or L):
Limit 2 Name: HVA1
Limit 2 Name: ABOVE 4200
Limit 2 Notification Code: MJ
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
MAJOR
HIGH
MINOR
LOW
MINOR
TOOLOW
MJ
SA
MN
NSA
MN
NSA
166

Advertisement

Table of Contents
loading

This manual is also suitable for:

586505000586505500

Table of Contents