Vertiv NetSure LMS1000 User Manual page 527

Lms data processing unit
Table of Contents

Advertisement

7.
Reinstall the modem circuit card onto the replacement CPU circuit card, if present. Replace the modem
cable, if present.
8.
Slide the replacement CPU circuit card into its mounting position, ensuring the rear edge connector is
firmly seated. Secure the circuit card by tightening the retaining screw located on the circuit card
assembly (this is also the RS 232 Connector Grounding Screw). In a 582140000/582140001/582126100
Power System, note that if a modem is installed, it also contains a bracket with a retaining screw.
9.
If external hardware fail alarms where connected to J4 on the existing circuit card, remove the supplied
top half of J4 from the replacement CPU circuit card. This piece is not used, and may be saved or
discarded. Attach the top half of J4 (removed from the old CPU circuit card) to the bottom half of J4
located on the replacement CPU circuit card.
10.
Remove the grounding wrist strap.
11.
586505000/586505500 LMS1000 Cabinet: Close the shelf door and secure with the two captive
fasteners (arrow on fastener points towards outside of cabinet).
or
582140000/582140001/582126100 Power System: Close the bay's front door.
12.
Reapply DC input power to the LMS1000 CPU circuit card.
13.
Log onto the system using the default level six password (6).
14.
Enter the command SYSTEM INIT.
Upload the LMS1000 Configuration
1.
Upload the configuration from a PC to the LMS1000 by following one of the procedures detailed next.
Uploading the Configuration from a PC to the LMS1000 using XMODEM
NOTE!
The communications parameters of the remote terminal must match the system's default
parameters. The default parameters are 8 data bits, 1 stop bit, and no parity. These defaults cannot be
changed.
a)
Log onto the system using the default level six password (6).
b)
Enter the command UPLOAD, then press ENTER. The following will be displayed.
UPLOAD using XMODEM Protocol with CRC error checking
You have up to 1 minute to initiate a file transfer.
this 1 minute period the system sends a 'C' character, which is the
synchronization character for starting an XMODEM CRC file transfer.
c)
At the PC, initiate a file transfer using XMODEM CRC protocol.
d)
When the transfer is complete, the following is displayed.
84 blocks received OK.
Upload Complete.
The number of blocks received may vary.
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
Each second during
527