Vertiv NetSure LMS1000 User Manual page 474

Lms data processing unit
Table of Contents

Advertisement

RETRIEVE-ALARM
(RTRV-ALM-{EQPT|ALL})
Referenced In: TR-NWT-000833, Issue 5, pg. 4-205
General Description: Instructs LMS1000 to send the current state of its alarm conditions associated with one
or more equipment units, facilities, etc. within LMS1000.
Related Commands: None
Related Messages: REPORT ALARM EQUIPMENT
LMS1000 Access Level: 1
LMS1000 Equivalent: ALARMS <t<n>>
LMS1000 Input Format Variations: The command code modifier COM is not supported.
<aid>
Specifying a value of ALL for the access identifier (<aid>) parameter requests retrieval of alarm conditions for all
access identifiers of the type defined by the command code modifier. Use of the command code modifier ALL
results in retrieval of all alarm conditions in LMS1000. If the command code modifier is ALL, the value of the
access identifier must be ALL. A NULL value is not permitted for this parameter. Invalid values received for
this parameter return an error response with the error code IIAC.
<ntfcncde>
Specifies the notification code parameter associated with the alarm conditions being retrieved. This parameter
is an attribute of the LMS1000 channel or limit configuration.
Valid values for this parameter are as follows:
CR
critical alarm
MJ
major alarm
MN
minor alarm
NULL
request retrieval of alarm conditions for all of the above codes
Invalid values for this parameter return an error response with the error code IDNV.
<condtype>
Specifies the condition type parameter of alarm conditions to be retrieved. A NULL value causes all conditions
classified as alarm conditions to be retrieved. This parameter is an attribute of the LMS1000 channel or limit
configuration. Invalid values for this parameter return an error response with the error code IDNV.
<srveff>
Specifies the service effect parameter caused by the alarm conditions to be retrieved. This parameter is an
attribute of the LMS1000 channel or limit configuration.
Valid values for this parameter are as follows:
SA
service-affecting condition
NSA
nonservice-affecting condition
NULL
request retrieval of alarm conditions for both of the above codes
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
474

Advertisement

Table of Contents
loading

This manual is also suitable for:

586505000586505500

Table of Contents