SET NETSURE SYSTEM BATTCURLIM

Description: Sets the VPS/NPS "system battery current limit" value.
Command Level: 6
Syntax:
SET NETSURE SYSTEM BATTCURLIM
SE N SY BATTC
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The following message is displayed if the setting was not accepted by the MCA.
Power system did not accept the new value, setting remains unchanged.
Related Commands: none
Example:
Command<6>: SET NETSURE SYSTEM BATTCURLIM Battery Current Limit: 275.0 Amps
Battery Current Limit: