SET NETSURE SYSTEM HVS
Description: Sets the VPS/NPS "high voltage shutdown" value.
Command Level: 6
Syntax:
SET NETSURE SYSTEM HVS
SE N SY HVS
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The MCA does not allow an adjustment which could result in a service interruption. Refer to the
VPS/NPS instruction manual's high voltage shutdown adjustment procedure for details.
The following message is displayed if the setting was not accepted by the MCA.
Power system did not accept the new value, setting remains unchanged.
Related Commands: none
Example:
Command<6>: SET N SYSTEM HVS
System How Voltage Shutdown: 59.50 VDC
System How Voltage Shutdown:
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA
391