SET NETSURE SYSTEM FLTVOLT
Description: Sets the VPS/NPS "float output voltage" value.
Command Level: 6
Syntax:
SET NETSURE SYSTEM FLTVOLT
SE N SY FLT
Comments: The current value is displayed, followed by a prompt to enter a new value.
Notes: The MCA does not allow an adjustment which could result in a service interruption. Refer to the
VPS/NPS instruction manual's float voltage adjustment procedure for details.
The following message is displayed if the setting was not accepted by the MCA.
Power system did not accept the new value, setting remains unchanged.
Related Commands: none
Example:
Command<6>: SET N SYSTEM FLTVOLT
Float voltage:
Float voltage:
Vertiv™
| NetSure™ LMS Data Processing Unit User Manual (Section 5847) | Rev. ZA