Only one AD-400/AD-401 can be linked at one
L
time. Ensure that no other PIM400 units are in link
mode during this process.
1. Make sure the batteries are installed in the AD-400/
AD-401. See Batteries on page 12 for information.
2. Make sure the PIM400 is in link mode.
For PIM400-TD2: Hold down one of the LINK
buttons. (LINK button 1 or 2 will assign the AD-400/
AD-401 door number).
For PIM400-485: Use SUS to put the PIM400-485
into LINK mode with the door number tab and assign
the AD-400/AD-401 door number. See the SUS User
Guide for more information.
3. Open the AD-400/AD-401 door.
4. Create a request-to-exit condition by holding down the
inside lever or crash bar.
If using a crash bar, Request to Exit (RTX) must be
L
installed.
If RTX is not installed, temporarily short the RTX input on the lock main PCB
during this procedure.
5. While holding down the lever or crash bar, present a card to the prox or mag card
reader. For a keypad reader, press the "#" key.
6. Continue to hold down the lever or crash bar until the AD-400/AD-401 Schlage button
starts to blink green, indicating that the link process has begun (approximately 8 seconds).
7. Release the inside lever or crash bar.
8. The Schlage button will blink green, and the beeper will beep.
The number of green blinks and beeps indicates the frequency channel number on
L
which the lock is linked to the PIM400 (example: 3 blinks and beeps = channel 3).
9. If the link fails, the Schlage button will blink red three (3) times and five (5) short beeps
will sound. The PIM400 will remain in link mode. Carefully repeat steps 1-8 above. If
repeated LINK attempts fail, change the frequency channel of the PIM400 and/or move
the PIM400, then repeat steps 3-7.
10. Test the lock for normal operation. See Test lock operation on page 9 for information.
Re-linking is required anytime the AD-400/AD-401 or the PIM400 is moved or replaced,
Dynamic Channel Switching is activated, deactivated, or the frequency channel is manually
changed.To re-link, repeat the procedure above. The AD-400/AD-401 link to the PIM400 is
retained in the event of power loss.
Link LED and beep reference
Lights
Beeps
1 Red,
1 Green
1 Green
1 Red
Z Green
1
3 Red
Z = Frequency channel number on which the lock is linked (1-10). The frequency channel
number of each PIM400 in the area should be known and recorded. Use this information to
make sure the AD-400/AD-401 linked to the intended PIM400.
8 • Schlage • AD-400 user guide
Link to a PIM400
0
One link request was sent to find a PIM400 in link mode. This will
repeat once and then the lock will stop trying to find a PIM400.
0
Successful RF packet transmission
0
Unsuccessful RF packet transmission
Z
Linking was successful
1
5
Linking was unsuccessful
During linking, the Schlage
button will blink red and
green. Green blinks indicate
successful packets and red
blinks indicate unsuccessful
packets. If you get several
red blinks, the lock and
PIM400 may still link, but you
may experience intermittent
communication in the future.
You should move the PIM400
closer to the lock, select
another RF channel or add
another PIM400.
Action