Omron R88M-K User Manual page 662

Ac servomotors/servo drives g5-series with built-in ethercat communications
Hide thumbs Also See for R88M-K:
Table of Contents

Advertisement

Appendices
Event name
Main Circuit Power Supply Undervoltage (AC Cutoff
Detected)
Meaning
If the Undervoltage Error Selection (3508 hex) is set to 1, a momentary power interruption occurred between L1 and L3
for longer than the value specified for the Momentary Hold Time. The voltage between the positive and negative
terminals in the main power supply converter dropped below the specified value while the Servo was ON.
Source
EtherCAT Master Function Module
Error attributes
Level
Effects
User program
Indicators
EtherCAT NET RUN
---
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
Insufficient power supply capacity
The electromagnetic contactor in the
main circuit power supply was
tripped.
A momentary power interruption
occurred.
A Servo Drive with 3-phase input
specifications was operated with a
single-phase power supply.
The Servo Drive failed.
Attached
None
information
Precautions/
"13" is displayed on the Servo Drive front panel and F113 is given as the AlarmCode (4001 hex)
Remarks
A-112
Source details
Minor fault
Recovery
Continues.
Operation
EtherCAT NET ERR
---
Data type
---
Remedy
Increase the power supply capacity.
Eliminate the cause of the failure of
the electromagnetic contactor on the
main circuit power supply, and then
turn ON the power again.
Review the power supply conditions
and prevent momentary power
interruption. Alternatively, increase
the Momentary Hold Time (3509 hex)
setting.
Make sure that the phases of the
power supply are set correctly before
you connect them.
Replace the Servo Drive.
G5-series AC Servomotors and Servo Drives User's Manual (with Built-in EtherCAT Communications)
Event code
04AB0000 hex
Slave
Detection
timing
Error reset (after
Log category
resetting slave
errors)
Power drive circuit is OFF for relevant slave.
EtherCAT LINK/ACT
---
Name
---
Prevention
None
Check the wiring of the main circuit
power supply.
Make sure that the power supply
conditions prevent momentary power
interruption.
Make sure that the phases of the
power supply are set correctly before
you connect them.
None
While power is
supplied to motor
System