Omron R88M-K User Manual page 410

Ac servomotors/servo drives g5-series with built-in ethercat communications
Hide thumbs Also See for R88M-K:
Table of Contents

Advertisement

9 Details on Servo Parameter Objects
Regeneration Resistor Selection
3016 hex
Setting range
0 to 3
Size
2 bytes (INT16)
*1 The default setting is 0 for a Drive with 100 V and 400 W, with 200 V and 750 W or greater, or with 400 V.
• The setting is different whether the Regeneration Resistor built in the Drive is directly used, or it is
removed and replaced by an External Regeneration Resistor. In the latter case, the resistor is
connected to the External Regeneration Resistor connection terminal.
Explanation of Set Values
Set value
0
Regeneration Resistor used: Built-in Resistor
The regeneration processing circuit operates and the Regeneration Overload Error (Error
No. 18.0) are enabled according to the Built-in Resistor (with approx. 1% duty).
1
Regeneration Resistor used: External Resistor
The regeneration processing circuit operates, and Regeneration Overload Error (Error No. 18.0)
cause a trip when the operating rate of the Regeneration Resistor exceeds 10%.
2
Regeneration Resistor used: External Resistor
The regeneration processing circuit operates, but Regeneration Overload Error (Error No. 18.0) do
not occur.
3
Regeneration Resistor used: None
The regeneration processing circuit and Regeneration Overload Error (Error No. 18.0) do not
operate, and all regenerative energy is processed by the built-in capacitor.
Precautions for Correct Use
Precautions for Correct Use
• Do not touch the External Regeneration Resistor. A burn injury may result.
• Always provide a temperature fuse or other protective measure when using an External
Regeneration Resistor. Regardless of whether the regeneration overload error is enabled or
disabled, the Regeneration Resistor can generate heat and may cause burning.
• To use the Built-in Regeneration Resistor, always set this object to 0.
External Regeneration Resistor Setting
3017 hex
Setting range
0 to 4
Size
2 bytes (INT16)
• Select the method to calculate the regeneration resistance load ratio, when the External Resistor is
selected in the Regeneration Resistor Selection (3016 hex = 1 or 2).
Explanation of Set Values
Set value
0
Regeneration load ratio is 100% when operating rate of the External Regeneration Resistor is
10%.
1
Reserved
2
Reserved
3
Reserved
4
Reserved
9-6
Unit
Access
Unit
Access
G5-series AC Servomotors and Servo Drives User's Manual (with Built-in EtherCAT Communications)
Default setting
RW
Description
Default setting
RW
Description
*1
Data attribute
3
PDO map
Not possible.
0
Data attribute
PDO map
Not possible.
All
C
All
C

Hide quick links:

Advertisement

Table of Contents