4 System Design
• Ground the motor's frame to the machine ground when the motor is on a movable shaft.
• Use a ground plate for the frame ground for each unit, as shown in the above diagrams, and ground to a
single point.
• Use ground lines with a minimum thickness of 3.5 mm
are as short as possible.
• A no-fuse breaker, surge absorber, and noise filter should be positioned near the input terminal block
(ground plate), and I/O lines should be separated and wired at the shortest distance.
Unit Details
Symbol
SG
Surge absorber
NF
Noise filter
SD
Servo Drive
SM
Servomotor
FC1
Clamp core
FC2
Clamp core
FC3
Clamp core
FC4
Clamp core
TB
Switch box
-
Controller
*1 A specified combination of Servo Drive and Servomotor must be used.
4-36
Name
Manufacturer
Okaya Electric
Industries Co., Ltd.
Okaya Electric
Industries Co., Ltd.
OMRON
OMRON
TDK
Konno Kogyosho
NEC TOKIN
Corporation
MICROMETALS
TDK
−
−
G5-series AC Servomotors and Servo Drives User's Manual (with Built-in EtherCAT Communications)
2
, and arrange the wiring so that the ground lines
Model
·
·
3-phase 200 VAC
R
A
V-781BXZ-4
SUP-EK5-ER-6
Single-phase 100/200 VAC (5 A)
3SUP-HU10-ER-6
3-phase 200 VAC (10 A)
3SUP-HU30-ER-6
3-phase 200 VAC (30 A)
3SUP-HL50-ER-6B
3-phase 200 VAC (50 A)
−
−
ZCAT3035-1330
RJ8035
ESD-SR-250
T400-61D
R88D-KN75H-ECT/-KN150H-ECT
ZCAT3035-1330
Except for the above
−
−
Comment
*1
*1
−
−
−
−
−