Omron R88M-K User Manual page 270

Ac servomotors/servo drives g5-series with built-in ethercat communications
Hide thumbs Also See for R88M-K:
Table of Contents

Advertisement

4 System Design
R88D-KN75H-ECT
Terminal Block Specifications, Left Terminal Block (TB1)
Symbol
L1
Main circuit power supply
input
L2
L3
B1
External Regeneration
Resistor connection
B2
terminals
*1
N
U
Motor connection
terminals
V
W
*1 The symbol "N" is found on G5-series AC Servo Drives with unit version 2.1 or later.
Precautions for Correct Use
Precautions for Correct Use
• Do not connect any External Regeneration Resistors between B1 and N (or NC).
Terminal Block Specifications, Right Terminal Block (TB2)
Symbol
L1C
Control circuit power
supply input
L2C
DB1
Dynamic Brake Resistor
control terminals
DB2
DB3
DB4
Frame ground
4-24
Name
R88D-KN H-ECT (7.5 kW):
3-phase 200 to 230 VAC (170 to 253 VAC) 50/60 Hz
280 to 325 VDC (238 to 357 VAC)
Connect an External Regeneration Resistor between B1 and B2.
Red
White
Blue
Green/
Yellow
Name
R88D-KN H-ECT:
Single-phase 200 to 230 VAC (170 to 253 VAC) 50/60 Hz
280 to 325 VDC (238 to 357 VAC)
These terminals are used to control the MC for externally
connected dynamic brake resistance. The output contact
specifications are 1 A max. at 300 VAC/100 VDC max.
Connect them if required.
Normally DB3 and DB4 are shorted.
When using an externally connected Dynamic Brake Resistor,
remove the short bar from between DB3 and DB4.
This is the ground terminal. Ground it to 100 Ω or less.
G5-series AC Servomotors and Servo Drives User's Manual (with Built-in EtherCAT Communications)
Function
These are the output terminals to the Servomotor.
Be sure to wire them correctly.
Function