Resetting Alarms Detected In Option Modules - YASKAWA SGD7S-****20A Series Product Manual

Servopack with mechatrolink-iii communications references, ac servo drive
Table of Contents

Advertisement

12.2 Alarm Displays

12.2.6 Resetting Alarms Detected in Option Modules

12.2.6 Resetting Alarms Detected in Option Modules
If any Option Modules are attached to the SERVOPACK, the SERVOPACK detects the pres-
ence and models of the connected Option Modules. If it finds any errors, it outputs alarms.
You can delete those alarms with this operation.
Information
Preparations
Always check the following before you clear an alarm detected in an Option Module.
• The parameters must not be write prohibited.
Applicable Tools
The following table lists the tools that you can use to reset Option Module configuration errors
and the applicable tool functions.
Digital Operator
SigmaWin+
Operating Procedure
Use the following procedure to reset alarms detected in Option Modules.
1.
Click the
maWin+.
2.
Select Reset Option Module Configuration Error in the Menu Dialog Box.
The Reset Option Module Configuration Error Dialog Box will be displayed.
3.
Select the Clear Check Box for the Option Modules from which to clear alarms and the
click the Execute Button.
12-46
• This operation is the only way to reset alarms for Option Modules. The alarms are not reset
when you reset other alarms or when you turn OFF the power supply to the SERVOPACK.
• Always remove the cause of an alarm before you reset the alarm.
Tool
Fn014
-
Setup
Reset Option Module
Configuration Error
Servo Drive Button in the workspace of the Main Window of the Sig-
Function
Operating Procedure
Reference
Σ
-7-Series Digital Operator Operating Manual
(Manual No.: SIEP S800001 33)
on page 12-46

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sigma-7-s series

Table of Contents