Leak Testing The Refrigerant System - Daewoo MATIZ Service Manual

Table of Contents

Advertisement

MANUAL CONTROL HEATING, VENTILATION, AND AIR CONDITIONING SYSTEM 7B – 7
LEAK TESTING THE REFRIGERANT
SYSTEM
Test for leaks whenever you suspect a refrigerant leak in
the system. You should also test for leaks whenever you
perform a service operation which results in disturbing
the lines or the connections. Leaks are commonly found
at the refrigerant fittings or at the connections. Leaks are
commonly caused by the following problems:
D Improper torque.
D Damaged O-ring seals.
D Dirt or lint on the O-ring seals.
Liquid Leak Detectors
Use a liquid leak detector solution on locations such as
fittings. Apply the solution to the area in question with
the swab that is supplied with the solution. Look for
bubbles to appear. This will indicate the existence and
location of any leak.
For areas where this is not practical, such as sections of
the evaporator and the condenser, an electronic leak de-
tector is more useful.
Electronic Leak Detectors
Follow the manufacturer's instructions for calibration,
operation, and maintenance of an electronic leak detec-
tor. Battery condition is especially important to the accu-
racy of a portable model. Set the detector to R-134a
before beginning the test.
Important: Electronic leak detectors are sensitive to
windshield washing solutions, solvents and cleaners,
and certain vehicle adhesives.
Surfaces must be clean to prevent false readings. Make
sure that all surfaces are dry to prevent damage to the
detector.
General Testing Instructions
D Follow the entire path of the refrigerant system.
D Completely circle each joint at 25 to 50 mm (1 to 2
inches) per second.
D Hold the probe tip within 6 mm (1/4 inch) of the sur-
face.
D Do not block the air intake.
DAEWOO M-150 BL2
The audible tone changes from 1 to 2 clicks per second
into a solid alarm if there is a leak. Adjust the balance
control to maintain 1 to 2 clicks per second.
Test all of the following areas, even after one leak has
been confirmed:
D Evaporator inlet and outlet.
D Receiver-drier inlet and outlet.
D Condenser inlet and outlet.
D Brazed and welded areas.
D Damaged areas.
D Hose couplings.
D Compressor rear head.
D All fittings and joints.
Testing Service Ports/Access Valves
The sealing cap is the primary seal for the service ports.
This cap contains a special leak-free O-ring. Make sure
that this cap is not missing or loose. Always use the cor-
rect cap.
Testing the Evaporator Core
Leaks in the evaporator core are difficult to find. Test the
evaporator core using the following procedure:
1. Run the blower fan at speed setting 4 for at least
15 minutes.
2. Turn the blower to the OFF position.
3. Wait for 10 minutes.
4. Remove the blower motor resistor. Refer to "Blower
Motor Resistor" in this section.
5. Insert the leak detector probe as close as possible to
the evaporator core. The detector will indicate a leak
with a solid alarm.
6. Use a flashlight to search for refrigerant oil in the core
surface.
Testing the Compressor Shaft Seal
1. Blow shop air behind and in front of the compressor
clutch/pulley for at least 15 seconds.
2. Wait 1 to 2 minutes.
3. Probe the area in front of the pulley. If the detector
emits a solid alarm, there is a leak.

Advertisement

Table of Contents
loading

This manual is also suitable for:

My2003

Table of Contents