Chapter 4: Diagnosing faults
Diagnostic procedure 8
Application terminal problem (continued)
8.4
Attach the failing
terminal directly to an
AM or IPE Module port.
Does it function?
NO
(Terminal
problem)
Use the portconfig
command to ensure
that the terminal port
is on (configured for
a terminal).
Is the display
functioning?
Stop
553-3211-510 Standard 1.0 October 1998
This procedure applies to CCR only.
YES
(Modem problem)
Note: An IPE Module port
is on an NT1R03 octopus
cable.
NO
Is the terminal a
VT220-compatible
ASCII terminal?
YES
Replace one or
both modems.
NO
YES
Go to
8.5
Is the terminal
a PC running
Reflection 4+?
YES
Go to
8.8
Replace the terminal
with an appropriate
terminal type.
NO