Mounting The Unit - Omron CS1W-NC113 Manual

Hide thumbs Also See for CS1W-NC113:
Table of Contents

Advertisement

Installation

3-2-2 Mounting the Unit

1, 2, 3...
Philips-head screwdriver
Follow the procedure outlined below to mount the Position Control Unit.
1. Hook the top of the PCU into the slot in the Backplane.
Hook
Backplane
2. Carefully insert the PCU into the connector on the Backplane.
3. Tighten the screw on the bottom with a Philips-head screwdriver. Provide
enough space around the PCU to enable easy mounting and dismounting,
and to ensure good ventilation as shown below.
Duct
20 mm min.
Backplane
PCU
20 mm min.
Duct
Note Tighten the screw at the bottom of the PCU to a torque of 0.4 N⋅m.
4. To remove the PCU, use a Philips-head screwdriver to loosen the screw at
the bottom of the PCU, and rotate the PCU upwards before dismounting.
Section
3-2
23

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs1w-nc213Cs1w-nc433Cs1w-nc233Cs1w-nc413Cs1w-nc133