Module 9002 Reading All Inputs Of A Plc Input/Output Unit - HEIDENHAIN TNC 426 PB/M Technical Manual

Table of Contents

Advertisement

6 – 390
With Module 9004 you can evaluate the rising or falling edge of the PLC
inputs.
Note
As of NC software 280 476-03, before the PLC program is converted, the
PLC outputs are reset.
As of NC software 280 476-03, the memories of the PLC outputs are also
reset.
As of NC software 280 476-09, an attempt is made to reset the PLC outputs
when a power fail occurs.

Module 9002 Reading all inputs of a PLC input/output unit

In PLC addresses you can read the current states of the PLC input/output unit.
(See "Mounting and Electrical Installation" on page 3 – 5).
The memory contents remain unchanged until you call this module or Module
9008. The module does not recognize whether a PLC input/output unit is
actually connected.
The program can be called only in the cyclic PLC program.
Call:
PS
B/W/D/K <Number of the PL>
0: First PLC input/output unit
1: Second PLC input/output unit
2: Third PLC input/output unit
3: Fourth PLC input/output unit
CM
9002
Error recognition:
Marker
Value
Meaning
M4203
0
Inputs were read
1
Error code in W1022
W1022
2
Invalid PL no.
24
Module was called in a spawn job or submit job
HEIDENHAIN Technical Manual TNC 426, TNC 430

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tnc 430 pa/mTnc 430 mTnc 426 cbTnc 430 caTnc 426 pbTnc 430 pa ... Show all

Table of Contents