Module 9103 Transmit string through data interface

You must first assign the interface to the PLC and initialize it with Module
9100.
Module 9103 transmits a string from one of the 16 string memories through
one of the two interfaces. Links to the PLC error file and PLC dialog file are
deleted. See "Error Messages" on page 3– 3.
Can only be called in a submit job or spawn job!
Call:
PS
B/W/D/K <Interface>
0: RS232
1: RS422
PS
K/B/W/D <Number of source string in the string buffer>
CM
9103
Error recognition:
Marker
Value
Meaning
M4203
0
String was transmitted
1
Error code in W1022
W1022
1
Incorrect interface or incorrect string number
12
No string end found
13
Interface not ready
14
Interface not assigned
15
Transmit buffer not empty
20
Module was not called in a spawn job or submit job