Device specifications
System data AC500-eCo V3 > Environmental conditions
Part no.
1SAP 187 400 R0014
1SAP 187 400 R0015

6.4 System data AC500-eCo V3

6.4.1 Environmental conditions

Table 31: Process and supply voltage
Parameter
Voltage
Protection against reverse polarity
Allowed interruptions of power supply, according to EN 61131-2
Parameter
Temperature
Humidity
Air pressure
154
Description
TA5220-SPF7: spring terminal block, removable, 7-pin, spring front,
cable front, 6 pieces per packing unit
TA5220-SPF8: spring terminal block, removable, 8-pin, spring front,
cable front, 6 pieces per packing unit
DC supply
NOTICE!
Exceeding the maximum power supply voltage (> 30 VDC) for process or
supply voltages could lead to unrecoverable damage of the system. The system
could be destroyed.
Operating
Horizontal mounting
Standard temperature
range
Wide temperature
range
Vertical mounting (output load reduced to 50 % per group)
Standard temperature
range
Wide temperature
range
Storage
Transport
Operating
Storage
3ADR010635, 2, en_US
Value
24 V (-15 %, +20 %)
Yes
Interruption < 10 ms, time between 2 interruptions >
1 s, PS2
Value
PM5012
PM5032
0 °C...+55 °C 0 °C...+60 °C
-
0 °C...+40 °C
-
-40 °C...+70 °C
-40 °C...+70 °C
Max. 95 %, without condensation
> 800 hPa / < 2000 m
> 660 hPa / < 3500 m
PM5052
PM5072
-20 °C...+70 °C
-20 °C...+40 °C