Goose Data Exchange - ABB Relion 650 Series Engineering Manual

Hide thumbs Also See for Relion 650 Series:
Table of Contents

Advertisement

Section 7
IEC 61850 communication engineering
LN
LN
GOOSE
GOOSE
Send
Send
FBs
with
monitoring
only
FBs
with
monitoring
and
commands
IEC08000364 V1 EN-US
Figure 60: IEC 61850: Communication interface principle
IEC 61850 has as a concept for the identification of all signals for communication that belong to a
function by a logical node as a placeholder. All signal information in command and monitoring
direction, which belongs to a function, is available within the logical node.
Whenever a function block is instantiated in ACT, PCM600 automatically generates the
corresponding logical node data. In
upper part is the visible function block in ACT and the lower part is the logical node data for the
function block.
7.1.2.1

GOOSE data exchange

The IEC 61850 protocol supports a method to directly exchange data between two or more IEDs.
This method is described in the IEC 61850–7–2 clause 15. The concept is based on sending a
multicast over the Ethernet. Whoever needs the information detects the telegram by its source
address and will read the telegram and deals with it. The telegrams are multicast sent and not
acknowledged by the receiver.
78
FBs
FBs
GOOSE
GOOSE
Receive
Receive
FB
AFL
LN
part
FB
AFL
LN
part
FB
AFL
LN
part
Figure 60
© Copyright 2011 ABB. All rights reserved
GOOSE
Receive
GOOSE
Send
Commands
Event
handler
Event
queue
IEC08000364.vsd
this is shown by two parts per function block. The
1MRK 511 245-UUS A
SEMOD58549-71 v4
650 series
Engineering manual

Advertisement

Table of Contents
loading

Table of Contents