Write Constant

The "Write Constant" object writes a fixed constant to the PLC when a touch key is pressed.
The "Write Constant" object is convenient: When it is used, sequence programs such as trans-
fer instructions are not required.
u u u u Contents of setting
Attribute
Control Input
Constant
Word Device
n n n n Important point
1) Write constant to a timer/counter
Even if "0" is written to the current value or set value of a timer/counter, the output contact in
the PLC is not reset. (Though the current value or set value becomes 0, the output contact
does not become OFF.)
To reset a timer/counter, execute an RST instruction in the sequence program or reset the
timer/counter using the switch function.
2) Data file transfer condition
" " indicates that transfer is enabled.
PLC
PLC memory type
PLC operation status
GOT memory type
PLC entry code
Enter a key which actuates write of a constant.
Enter a fixed value to be written to a word device.
Enter a word device to which the fixed value is written.
Enter "Data Size" and "Changed Value" (Current or Preset) also.
FX Series
:RAM
:EEPROM
*1 When the read/write destination
is a data register, data can be
transferred without regard to the
memory type.
:RUN
:Flush memory
:While entry
code is regis-
tered (while
write is inhib-
ited)
Creation of Display Screens (FX-PCS-DU/WIN-E) 9
Contents of setting
:EPROM *1
:RAM
:STOP
:RUN
:Flush memory
:While entry
:While entry
code is
code is regis-
unlocked or is
tered (while
not registered
write is inhib-
ited)
A Series
:EPROM
:STOP
:While entry
code is
unlocked or is
not registered
9-48