Figure 6-7
6.2 E5-ENET/E5-ENET-B and Fan Option, EDCM, E5-
SM4G/E5-SM8G-B Cabling
E5-ENET/E5-ENET-B and EDCM Modules
The following cabling procedures apply to E5-ENET/E5-ENET-B,EDCM and E5-SM4G/E5-
SM8G-B cards in the latest EAGLE.
When the Database Communications Module (E5-ENET/E5-ENET-B) cards have been
1.
configured in the system, run the Ethernet cables straight through.
The Ethernet cables have a DB26 connector on the system end, and a RJ45 on the other
2.
end of the cable.
One cable is required for each E5-ENET/E5-ENET-B card.
On the system end (DB26), if the card is in slots 1,3,5, or 7, the cable is run down the
3.
right side of the frame (as seen from the back of the frame).

E5-ENET/E5-ENET-B and Fan Option, EDCM, E5-SM4G/E5-SM8G-B Cabling

LAN Ethernet Cable Installation
Chapter 6
6-15