The stripped cable must fill lug completely to the end of the barrel of the lug and
be visible in the end window of the lug.
Crimp #6 American Wire Gauge (AWG) lug with window on the cable, using an
3.
embossing crimper.
Apply a small amount of non oxidizing grease to the mounting holes on a copper
4.
system ground bar, Non oxidizing grease is not needed on a tin ground bar, where
the lug contacts the ground bar.
Crimp a #6 AWG lug with a window on the cable.
5.
Use an embossing crimper. The stripped cable must fill lug completely to the end
of the barrel of the lug and be visible in the end window of the lug.
warning:
All logic ground connections must be made to the system ground bar.
Figure 5-20
System Logic Ground Bar and Cable
Frame Ground and Logic Ground Cabling Procedures